AAC 1350 Conductor

 

Concentric lay stranded Aluminium Conductor ( AAC) is made up of one or more strands of hard drawn 1350 aluminum alloy. These conductors are used in low, medium and high voltage overhead lines. AAC has seen extensive use in urban areas where spans are usually short but high conductivity us required. The excellent corrosion resistance of aluminium has made AAC a conductor of choice in coastal areas. Because of its relatively poor strength to weight ratio, AAC had limited use in transmission lines and rural distribution because of long spans utilized. All aluminium conductors are made up of one or more strands of aluminium wire dep.

 


Product Detail

Packaging & Shipping

Product Tags

Application:

All Aluminum Conductor is also known as aluminium stranded conductor. It is manufactured from electrolytically refined aluminium, with a minimum purity of 99.7%.

Standard:

Aluminum stranded conductor are basic design to BS 215-1 / BS EN 50182 / IEC 61089 / ASTM B 231/B 231M / DIN 48201-5 standards

Specification:

All Aluminum Conductor ELECTRICAL PROPERTIES

Density@20°C

2.703 kg/dm
Temperature Coefficient@20°C

0.00403 (°C)

Resistivity@20°C

0.028264

Linear Expansivity

23 x10 -6 (°C)

SERVICE CONDITIONS:

Ambient Temperature -5°C – 50°C
Wind Pressure 80 – 130kg/m²
Seismic Acceleration 0.12 – 0.05g
Isokeraunic level 10 – 18
Relative Humidity 5 – 100%

All Aluminum Conductor CONSTRUCTION PARAMETERS ASTm B 231/B 231m

Code Nominal Area Stranding Overall
Diameter
Weight Rated
Strength
Electrical
Resistance
Current
Rating*
  AWG&MCM mm² No.x mm mm Kg/Km KN Ω/Km A
Peachbell 6 13.3 7/1.56 4.68 36.6 2.53 2.1477 75
Rose 4 21.1 7/1.96 5.88 58.2 3.91 1.3606 99
Iris 2 33.6 7/2.47 7.41 92.6 5.99 0.8567 132
Pansy 1 42.4 7/2.78 8.34 116.6 7.3 0.6763 153
Poppy 1/0.0 53.5 7/3.12 9.36 147.2 8.84 0.5369 176
Aster 2/0.0 67.4 7/3.50 10.5 185.7 11.1 0.4267 203
Phlox 3/0.0   85 7/3.93 11.79 233.9 13.5 0.3384 234
Oxlip 4/0.0 107.2 7/4.42 13.26 295.2 17 0.2675 270
Valerian 250 126.7 19/2.91 14.55 348.6 20.7 0.2274 299
Tulip 336.4 170.5 19/3.38 16.9 469.5 27.3 0.1686 359
Orchid 636 322.3 37/3.33 23.31 886.9 50.4 0.0892 530
Magnolia 954 483.4 37/4.08 28.56 1331 72.6 0.0594 676

All Aluminum Conductor CONSTRUCTION PARAMETERS IEC 61089

Code Nominal Area Stranding Overall
Diameter
Weight Rated
Strength
Electrical
Resistance
Current
Rating*
  mm² No.x mm mm Kg/Km KN Ω/Km A
10 10 7/1.35 4.05 27.4 1.95 2.8633 62
16 16 7/1.71 5.13 43.8 3.04 1.7896 84
25 25 7/2.13 6.39 68.4 4.5 1.1453 110
40 40 7/2.70 8.1 109.4 6.8 0.7158 147
63 63 7/3.39 10.17 172.3 10.39 0.4545 195
100 100 19/2.59 12.95 274.8 17 0.2877 259
125 125 19/2.89   14.45 343.6 21.25 0.2302 297
160 160 19/3.27   16.35 439.8 26.4 0.1798 345
200 200 19/3.66 18.3 549.7 32 0.1439 396
250 250 19/4.09 20.45 687.1 40 0.1151 454
315 315 37/3.29 23.03 867.9 51.97 0.0916 522
630 630 61/3.63 32.67 1738.3 100.8 0.0458 789

  • Previous:
  • Next:

  • 1-5KM per roll. Packed by steel drum . Other packing available according to client`s Request.

    Sheath Mark:

    The following printing(white hot foil indentation)is applied at 1meter intervals. a. Supplier: Guanglian or as customer required; b. Standard Code(Product Type, Fiber Type,Fiber Count); c. Year of manufacture: 7 years; d. Length marking in meters.

    Port:

    Shanghai/Guangzhou/Shenzhen

    Lead Time:
    Quantity(KM) 1-300 ≥300
    Est.Time(Days) 15 To be begotiated!
    Note:

    The Packing standard and details as above is estimated and final size & weight shall be confirmed before shipment.  

    Packaging-Shipping

    The cables are packed in carton, coiled on Bakelite & steel drum. During transportation, right tools should be used to avoid damaging the package and to handle with ease. Cables should be protected from moisture,kept away from high temperature and fire sparks,protected from over bending and crushing,protected from mechanical stress and damage.

    Leave Your Message

    Write your message here and send it to us