Application:
All Aluminum Conductor is also known as aluminium stranded conductor. It is manufactured from electrolytically refined aluminium, with a minimum purity of 99.7%.
Standard:
Aluminum stranded conductor are basic design to BS 215-1 / BS EN 50182 / IEC 61089 / ASTM B 231/B 231M / DIN 48201-5 standards
Specification:
All Aluminum Conductor ELECTRICAL PROPERTIES
Density@20°C |
2.703 kg/dm |
Temperature Coefficient@20°C |
0.00403 (°C) |
Resistivity@20°C |
0.028264 |
Linear Expansivity |
23 x10 -6 (°C) |
SERVICE CONDITIONS:
Ambient Temperature | -5°C – 50°C |
Wind Pressure | 80 – 130kg/m² |
Seismic Acceleration | 0.12 – 0.05g |
Isokeraunic level | 10 – 18 |
Relative Humidity | 5 – 100% |
All Aluminum Conductor CONSTRUCTION PARAMETERS ASTm B 231/B 231m
Code | Nominal Area | Stranding | Overall Diameter |
Weight | Rated Strength |
Electrical Resistance |
Current Rating* |
|
AWG&MCM | mm² | No.x mm | mm | Kg/Km | KN | Ω/Km | A | |
Peachbell | 6 | 13.3 | 7/1.56 | 4.68 | 36.6 | 2.53 | 2.1477 | 75 |
Rose | 4 | 21.1 | 7/1.96 | 5.88 | 58.2 | 3.91 | 1.3606 | 99 |
Iris | 2 | 33.6 | 7/2.47 | 7.41 | 92.6 | 5.99 | 0.8567 | 132 |
Pansy | 1 | 42.4 | 7/2.78 | 8.34 | 116.6 | 7.3 | 0.6763 | 153 |
Poppy | 1/0.0 | 53.5 | 7/3.12 | 9.36 | 147.2 | 8.84 | 0.5369 | 176 |
Aster | 2/0.0 | 67.4 | 7/3.50 | 10.5 | 185.7 | 11.1 | 0.4267 | 203 |
Phlox | 3/0.0 | 85 | 7/3.93 | 11.79 | 233.9 | 13.5 | 0.3384 | 234 |
Oxlip | 4/0.0 | 107.2 | 7/4.42 | 13.26 | 295.2 | 17 | 0.2675 | 270 |
Valerian | 250 | 126.7 | 19/2.91 | 14.55 | 348.6 | 20.7 | 0.2274 | 299 |
Tulip | 336.4 | 170.5 | 19/3.38 | 16.9 | 469.5 | 27.3 | 0.1686 | 359 |
Orchid | 636 | 322.3 | 37/3.33 | 23.31 | 886.9 | 50.4 | 0.0892 | 530 |
Magnolia | 954 | 483.4 | 37/4.08 | 28.56 | 1331 | 72.6 | 0.0594 | 676 |
All Aluminum Conductor CONSTRUCTION PARAMETERS IEC 61089
Code | Nominal Area | Stranding | Overall Diameter |
Weight | Rated Strength |
Electrical Resistance |
Current Rating* |
mm² | No.x mm | mm | Kg/Km | KN | Ω/Km | A | |
10 | 10 | 7/1.35 | 4.05 | 27.4 | 1.95 | 2.8633 | 62 |
16 | 16 | 7/1.71 | 5.13 | 43.8 | 3.04 | 1.7896 | 84 |
25 | 25 | 7/2.13 | 6.39 | 68.4 | 4.5 | 1.1453 | 110 |
40 | 40 | 7/2.70 | 8.1 | 109.4 | 6.8 | 0.7158 | 147 |
63 | 63 | 7/3.39 | 10.17 | 172.3 | 10.39 | 0.4545 | 195 |
100 | 100 | 19/2.59 | 12.95 | 274.8 | 17 | 0.2877 | 259 |
125 | 125 | 19/2.89 | 14.45 | 343.6 | 21.25 | 0.2302 | 297 |
160 | 160 | 19/3.27 | 16.35 | 439.8 | 26.4 | 0.1798 | 345 |
200 | 200 | 19/3.66 | 18.3 | 549.7 | 32 | 0.1439 | 396 |
250 | 250 | 19/4.09 | 20.45 | 687.1 | 40 | 0.1151 | 454 |
315 | 315 | 37/3.29 | 23.03 | 867.9 | 51.97 | 0.0916 | 522 |
630 | 630 | 61/3.63 | 32.67 | 1738.3 | 100.8 | 0.0458 | 789 |
1-5KM per roll. Packed by steel drum . Other packing available according to client`s Request.
Sheath Mark:
The following printing(white hot foil indentation)is applied at 1meter intervals. a. Supplier: Guanglian or as customer required; b. Standard Code(Product Type, Fiber Type,Fiber Count); c. Year of manufacture: 7 years; d. Length marking in meters.
Port:
Shanghai/Guangzhou/Shenzhen
Lead Time:
Quantity(KM) | 1-300 | ≥300 |
Est.Time(Days) | 15 | To be begotiated! |
Note:
The Packing standard and details as above is estimated and final size & weight shall be confirmed before shipment.
The cables are packed in carton, coiled on Bakelite & steel drum. During transportation, right tools should be used to avoid damaging the package and to handle with ease. Cables should be protected from moisture,kept away from high temperature and fire sparks,protected from over bending and crushing,protected from mechanical stress and damage.